Programmable Logic Controller

KV-8000 series

Catalogs View Catalog

High speed I/O unit KV-SIR32XT

KV-SIR32XT - High speed  I/O unit

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-SIR32XT

Type

High-speed I/O unit

External connection method

Connector (MIL specification)*1

Input

Number of inputs

32 points

Input mode

24 VDC mode, 5 VDC mode*2 (with overvoltage protection function*3)

Maximum input voltage

24 VDC mode: 28.8 VDC
5 VDC mode: 6.0 VDC

Rated input voltage

24 VDC mode: 24 VDC, 5.1 mA
5 VDC mode: 5 VDC, 8.8 mA

Minimum ON voltage

24 VDC mode: 19 V
5 VDC mode: 3.5 V

Maximum OFF current

24 VDC mode: 1.5 mA

Maximum OFF voltage

5 VDC mode: 1.5 V

Common method

16 points/1 common (2 terminals)*4

Input time constant

1 μs/10 μs/20 μs/100 μs/500 μs/1 ms/5 ms/10 ms/50 ms

Input impedance

24 VDC mode: 4.4 kΩ
5 VDC mode: 350 Ω

Output

Number of outputs

32 points

Output mode

MOSFET (sink) (with overcurrent protection function)*5

Rated load

30 VDC, 0.2 A (1.6 A/1 common)

Leakage current at OFF

100 μA or less

Residual voltage at ON

0.5 VDC or less

Common method

16 points/1 common (2 terminals)*4

Operation time

OFF to ON: 1 μs or less: (Load: 5 mA to 200 mA)
ON to OFF: 5 μs or less: (Load: 5 mA to 200 mA)

Internal current consumption

130 mA or less

Weight

Approx. 190 g

*1 Connectors for connector-type I/O units are not included XC Series Terminal Block Conversion Unit is available.
*2 5 VDC mode can only be used with IN100 to IN115.
*3 If an overvoltage is detected, all inputs (IN100 to IN115) in the shared commons will be turned OFF until the power is cycled or until PRG is switched to RUN.
*4 The four input and output COMs (input COM0 and COM1, and output COM2 and COM3) are independent. For each COM, those with two terminals are short-circuited internally.
*5 If an overcurrent is detected at even one point, protection operation (output OFF) will be enforced for all of the outputs in the shared commons (COM2: OUT200 to 215, COM3: OUT300 to 315) and automatic recovery will be repeated until the cause is eliminated.

Other Models